Understanding Boiler Pressure Controls - Boiling Point

WEBVTT
Kind: captions
Language: en

00:00:00.030
one thing I've learned is to get people
00:00:01.400 00:00:01.410 a lot smarter than me to talk about
00:00:03.409 00:00:03.419 things that I have no clue about well
00:00:06.349 00:00:06.359 dude wolf was so popular last week who
00:00:08.600 00:00:08.610 thought that we would do something with
00:00:10.009 00:00:10.019 him again so this week we're going to
00:00:11.749 00:00:11.759 talk about Honeywell pressure trolls
00:00:13.370 00:00:13.380 today on the boiling point
00:00:27.760 00:00:27.770 pressure controls like this are common
00:00:30.080 00:00:30.090 sight on a firetube boiler but often
00:00:33.710 00:00:33.720 times it's confusing why we have for
00:00:36.230 00:00:36.240 which one does what and having them set
00:00:39.800 00:00:39.810 properly is an important part of making
00:00:41.780 00:00:41.790 your boiler operate correctly so let's
00:00:44.299 00:00:44.309 take a look at these controls and
00:00:45.910 00:00:45.920 examine the use the purpose and the
00:00:49.640 00:00:49.650 proper setting for each of them like any
00:00:52.390 00:00:52.400 important control on a boiler water
00:00:55.400 00:00:55.410 level control pressure control we
00:00:57.950 00:00:57.960 typically have more than one instrument
00:01:00.620 00:01:00.630 doing that job that's just to back up
00:01:02.690 00:01:02.700 for safety purposes so with four
00:01:05.570 00:01:05.580 controls like this two of them are
00:01:07.760 00:01:07.770 dedicated to shutting the boiler off in
00:01:09.859 00:01:09.869 the case of high pressure the first one
00:01:13.219 00:01:13.229 to normally shut the boiler down on an
00:01:15.680 00:01:15.690 increase of pressure is the operating
00:01:17.780 00:01:17.790 control the operating control will break
00:01:21.530 00:01:21.540 open the limit circuit of the boiler and
00:01:24.380 00:01:24.390 turn the burner off when pressure hits
00:01:26.900 00:01:26.910 its setpoint
00:01:28.180 00:01:28.190 currently this one is set for 60 psi and
00:01:31.760 00:01:31.770 we can watch as the pressure increases
00:01:34.779 00:01:34.789 we can see that mercury bulb trip once
00:01:38.930 00:01:38.940 the boilers firing if there's
00:01:40.460 00:01:40.470 insufficient load for the boiler to stay
00:01:42.499 00:01:42.509 on that pressure will increase and it
00:01:46.580 00:01:46.590 will trip and open up that circuit
00:01:49.240 00:01:49.250 oftentimes this operating control is
00:01:51.770 00:01:51.780 misunderstood because the name implies
00:01:54.109 00:01:54.119 that it determines where the boiler
00:01:55.910 00:01:55.920 operates at pressure wise but in fact it
00:01:59.180 00:01:59.190 really cuts the boiler off at a certain
00:02:01.430 00:02:01.440 limit so typically our operating
00:02:03.680 00:02:03.690 pressure control should be set and what
00:02:06.380 00:02:06.390 we would want to be the highest pressure
00:02:08.270 00:02:08.280 that we want to see on the boiler at any
00:02:10.580 00:02:10.590 time so if we operated normally at 120
00:02:13.850 00:02:13.860 psi we may want to shut the boiler off
00:02:16.820 00:02:16.830 at 140 not because we're trying to hold
00:02:19.370 00:02:19.380 140 but because we want the boiler to
00:02:21.740 00:02:21.750 stay on as long as possible so that if
00:02:24.080 00:02:24.090 the load resumes we don't have to go
00:02:26.449 00:02:26.459 through the whole sequence of operation
00:02:28.160 00:02:28.170 and start it back up our high steam
00:02:32.270 00:02:32.280 pressure limit or high limit is it has
00:02:35.990 00:02:36.000 the same function in that it opens the
00:02:37.880 00:02:37.890 operating limit of the boiler on
00:02:39.860 00:02:39.870 to rise but it's also manual reset so
00:02:43.130 00:02:43.140 that if our operating limit fails to
00:02:45.229 00:02:45.239 function and we trip on our high limit
00:02:47.750 00:02:47.760 we get an indication because we have to
00:02:50.390 00:02:50.400 go out there and reset it manually that
00:02:52.399 00:02:52.409 something's wrong with our operating
00:02:54.050 00:02:54.060 pressure control or that they're set too
00:02:56.119 00:02:56.129 close together so we can watch that trip
00:02:59.199 00:02:59.209 so as the pressure increases past its
00:03:02.330 00:03:02.340 set point it's going to break and that's
00:03:10.309 00:03:10.319 going to shut down the boiler even if
00:03:12.800 00:03:12.810 the pressure drops on the boiler it's
00:03:14.809 00:03:14.819 not going to reset itself it's going to
00:03:18.740 00:03:18.750 require a manual reset many original old
00:03:22.970 00:03:22.980 controls on earlier generations of
00:03:26.089 00:03:26.099 boilers will have these mercury switches
00:03:27.979 00:03:27.989 the benefit of a mercury switch is it
00:03:30.289 00:03:30.299 gives you a visual indication of whether
00:03:32.449 00:03:32.459 the switch is made which is very
00:03:34.460 00:03:34.470 convenient but unfortunately they have
00:03:36.470 00:03:36.480 mercury in them which is something that
00:03:38.330 00:03:38.340 they're frowning on in many facilities
00:03:41.660 00:03:41.670 so the replacement for that is a micro
00:03:45.409 00:03:45.419 switch style control what we lose is an
00:03:48.379 00:03:48.389 actual visual indication of its trip
00:03:52.099 00:03:52.109 point and we're going to have to rely on
00:03:54.129 00:03:54.139 listening for the boiler to shut down
00:03:56.319 00:03:56.329 etc in order to set that up
00:03:59.479 00:03:59.489 so these two controls serve the purpose
00:04:02.569 00:04:02.579 of starting and stopping the boiler this
00:04:04.699 00:04:04.709 one routinely but this one only in the
00:04:06.770 00:04:06.780 event that the operating limit doesn't
00:04:08.449 00:04:08.459 work the firing the firing rate control
00:04:11.900 00:04:11.910 is actually the tool we use to try to
00:04:13.849 00:04:13.859 maintain the pressure on the boiler that
00:04:16.099 00:04:16.109 we desire when there's a load on the
00:04:17.810 00:04:17.820 boiler it actually uses a three wire
00:04:20.960 00:04:20.970 configuration commonly referred to a
00:04:23.510 00:04:23.520 series ninety has a slide wire
00:04:25.900 00:04:25.910 potentiometer in there which gives
00:04:27.890 00:04:27.900 information to the firing rate motor to
00:04:30.680 00:04:30.690 position the burner to match the load it
00:04:33.080 00:04:33.090 has a set point and the set point on
00:04:35.420 00:04:35.430 your firing rate controls basically the
00:04:37.279 00:04:37.289 point which it will tell the burner to
00:04:39.500 00:04:39.510 run at high fire the differential on
00:04:43.400 00:04:43.410 this controls referred to as additive
00:04:45.800 00:04:45.810 because whatever that differential is 5
00:04:48.920 00:04:48.930 pounds 10 pounds 15 pounds that above
00:04:52.130 00:04:52.140 the
00:04:53.110 00:04:53.120 point is where you're going to be in low
00:04:54.580 00:04:54.590 fire so the firing rate control if it's
00:04:58.000 00:04:58.010 not properly coordinated with the
00:04:59.770 00:04:59.780 operating limit you could have the
00:05:01.930 00:05:01.940 boiler tripping on pressure before
00:05:04.270 00:05:04.280 getting down to low fire and we call
00:05:06.310 00:05:06.320 that short cycling so we always want our
00:05:09.040 00:05:09.050 firing rate control set so that the
00:05:11.230 00:05:11.240 burners at its minimum input before our
00:05:14.560 00:05:14.570 operating limit trips and that's why we
00:05:17.290 00:05:17.300 don't set the operating limit at where
00:05:19.390 00:05:19.400 we want the fire the pressure to be we
00:05:22.750 00:05:22.760 set it where it's at the highest we
00:05:25.810 00:05:25.820 would really want to see on the system
00:05:27.760 00:05:27.770 an additional control that we often see
00:05:31.150 00:05:31.160 on a boiler is a low fire hold and the
00:05:33.790 00:05:33.800 point of a low fire hold is basically to
00:05:36.640 00:05:36.650 get a certain amount of pressure on the
00:05:39.010 00:05:39.020 boiler before allowing the boiler to
00:05:41.590 00:05:41.600 come out of the low fire position and
00:05:43.810 00:05:43.820 that's important because if we take a
00:05:45.550 00:05:45.560 cold boiler and we put full fire into
00:05:49.540 00:05:49.550 that unit we're going to thermally shock
00:05:51.490 00:05:51.500 it we're going to stress the tubes and
00:05:53.500 00:05:53.510 refractory so this is sort of an
00:05:55.659 00:05:55.669 insurance policy to prevent us from
00:05:58.170 00:05:58.180 firing the boiler hard before we
00:06:00.400 00:06:00.410 actually have steam in the boiler so
00:06:03.400 00:06:03.410 basically a summary on where these are
00:06:05.500 00:06:05.510 set generally are our high steam limit
00:06:08.560 00:06:08.570 is going to be set below our relief
00:06:10.540 00:06:10.550 valve setting on our boiler and
00:06:12.610 00:06:12.620 definitely below the maximum allowable
00:06:14.529 00:06:14.539 working pressure of the boiler because
00:06:16.570 00:06:16.580 its job is to prevent us from putting
00:06:19.270 00:06:19.280 excess pressure on the boiler our
00:06:21.360 00:06:21.370 operating limit we're going to put at
00:06:23.770 00:06:23.780 the highest pressure we would normally
00:06:25.629 00:06:25.639 want to see on our system so we may
00:06:27.790 00:06:27.800 operate when we have a load at 110 125
00:06:32.080 00:06:32.090 psi something appropriate for your plant
00:06:34.930 00:06:34.940 but at some point we're going to want to
00:06:36.939 00:06:36.949 turn the burner off so we'll put this at
00:06:40.089 00:06:40.099 the highest pressure that we care to see
00:06:42.279 00:06:42.289 on the system our firing rate control is
00:06:45.520 00:06:45.530 the workhorse
00:06:46.390 00:06:46.400 it's what's actually maintaining a
00:06:48.300 00:06:48.310 specific pressure on the boiler at any
00:06:51.189 00:06:51.199 given load and so this is the go-to for
00:06:55.330 00:06:55.340 adjusting our target pressure if we want
00:06:58.060 00:06:58.070 five more pounds on the boiler when it's
00:07:00.310 00:07:00.320 running we're going to adjust our firing
00:07:02.500 00:07:02.510 rate control and then we're going to
00:07:04.300 00:07:04.310 adjust our operating control so that we
00:07:05.980 00:07:05.990 don't shut
00:07:06.490 00:07:06.500 down before we get too low fire on the
00:07:10.120 00:07:10.130 firing rate control because that'll be
00:07:11.470 00:07:11.480 short cycling the low fire hold on a low
00:07:15.520 00:07:15.530 pressure boiler that might be set as low
00:07:17.470 00:07:17.480 as two or three pounds on a water-tube
00:07:20.110 00:07:20.120 boilers on to come out of low fire until
00:07:23.590 00:07:23.600 we've attained a hundred psi to develop
00:07:26.440 00:07:26.450 proper circulation on the boiler this is
00:07:29.140 00:07:29.150 not a substitute for attending the
00:07:32.800 00:07:32.810 boiler and warming it up slowly
00:07:34.600 00:07:34.610 and properly it's simply there is a
00:07:36.580 00:07:36.590 safeguard in case the boiler is
00:07:39.159 00:07:39.169 unattended for some reason while it's
00:07:40.990 00:07:41.000 warming up we are pumped that spring is
00:07:44.050 00:07:44.060 finally here and it's not so stinking
00:07:46.180 00:07:46.190 cold lots of equipment out getting
00:07:48.130 00:07:48.140 maintenance ready to go to the next
00:07:49.450 00:07:49.460 jobsite Jude Wolfe is always great to
00:07:52.300 00:07:52.310 have in fact the last video that we did
00:07:54.750 00:07:54.760 2,000 views in just a week and a half or
00:07:57.700 00:07:57.710 so so make sure that you check him out
00:07:59.620 00:07:59.630 on a lot of our other videos also on
00:08:01.960 00:08:01.970 that boiler university video right here
00:08:04.450 00:08:04.460 and make sure you check all of our
00:08:06.430 00:08:06.440 social media right over here and we'll
00:08:09.460 00:08:09.470 see you next time on the boiling point
00:08:29.740 00:08:29.750 you
Office location
Engineering company LOTUS®
Russia, Ekaterinburg, Lunacharskogo street, 240/12

Phone: +7 343 216 77 75

E-mail: info@lotus1.ru

Sales phone

Russia: +7 343 216 77 75

WhatsApp: +79122710308